Fire Detection & Alarm System Maintenance

A Fire Detection & Alarm System is an active electrical safety system designed to detect fire conditions, alert occupants, and initiate an emergency response. Section 6 of Australian Standard AS 1851 covers the routine servicing of fire detection and alarm systems to ensure they are being maintained and are working.

Fire Alarm, Thumbnail (Five-Yearly)

Maintenance requirements of fire detection and alarm systems are set out in the conditions of occupation for a building, Australian Standard AS 1851, manufacturers documentation and the operations and maintenance manual for the system and associated equipment.

This document helps users understand the maintenance requirements of fire detection and alarm systems, and their respective components. It does this by first defining the components of a system (extracted from AS 1851) and the associated maintenance requirements and frequency of maintenance of each component.

According to AS 1851, all routine service records must include pass/fail criteria captured at the time of service. For fire detection and alarm systems these records must be either as a hardcopy logbook or electronic log. Immediately after the completion of the routine service activity, a hardcopy of the service record (irrespective if it is a paper-based logbook or electronic log) must be left on site.

Fire Detection & Alarm System Component Maintenance Requirements

 

Item of EquipmentMonthly6-MonthlyYearly5-Yearly

Control and Indicating Equipment

✔   
External Alarm (Bell or Strobe)✔   
Battery Enclosure✔   
Occupant Warning System✔   
Visual Indicators (Filament Indicators, Light Emitting Diodes, Liquid Crystal Dispays and the like).✔ ✔ 
Zone Block Plan✔   

Special Hazard Systems

  • Local Control Station (LCS)
  • Visual Warning Device (Signs: Do Not Enter, Evacuate, Fire Alarm, System Inoperative)
  • Actuator Circuits
  • Actuators (Resettable)
 ✔  
Manual Call Points (Break Glass Alarms)  ✔ 
Warning Devices  ✔ 
Controls, Keypads & Switches  ✔ 
Batteries  ✔ 

Fire Detectors

  ✔ 
Heat & Smoke Alarms  ✔ 
Occupant Warning Systems  ✔✔

System Functions

  • Alarm Acknowledgement Facility
  • Alarm Investigation Facility
  ✔ 
Equipment with a defined service life (i.e. expiry date)  ✔ 
Protected Area Survey  ✔ 
Systems Interface  ✔✔
Smoke Hazard Management Systems (Fire Fan Control Panel)  ✔ 

Special Hazard Systems

  • Suppression System Status (Container Levels, Pressure Switches, Pump Controllers, Isolation Valves, Directional Valves  and the like).
  • System Initiation Discharge Time
  • Agent Release Indicator (e.g. Pressure Switch)
  ✔ 

Fire Alarm Control Panel Signals

  • Supervised Circuits
  • Fault Signals (Collective Circuits)
  • Power Supply Supervision
  • Alarm Verification Facility (Functional Test)
   ✔
Addressable Short Circuit Isolator   ✔
Monitoring Connection   ✔