The purpose of these tests is to ensure that where an isolate or disable condition is present at each FDCIE (main or distributed CIE), that the required signal is present (audibly and visually) and that where the system is monitored that the signal is also transmitted to the monitoring service provider.
Typically the isolate/disable function is displayed at the FDCIE as a yellow isolate signal, often paired with an audible signal that can be muted (silenced). For FDCIE fitted with a Liquid Crystal Display (LCD), the condition will typically also indicate the condition of each isolate or disable condition present, with a total number of isolate or disable conditions being also indicated on the display.
This item in the table would be better listed as THREE separate functional test requirements as follows;
| Item No | Item | Action required and pass/fail requirement | Pass | Fail | Comment |
|---|
| 1.6a | Isolate/Disable (Main FDCIE) | For each main fire detection control and indicating equipment (FDCIE), INITIATE and TEST the operation of an isolate/disable function and confirm that each required common or general visual and audible indication operates. | | | |
| 1.6b | Isolate/Disable (distributed FDCIE, where fitted) | For each connected (sub) FDCIE, TEST the operation of an isolate/disable function and CONFIRM that each required common or general visual and audible indication operates at the main FDCIE. | | | |
| 1.6c | Isolate/Disable (Alarm Signalling Equipment) | VERIFY where fitted the isolate/disable function initiated at the fire alarm control panel (FACP) is received by the monitoring service provider via the Alarm Signalling Equipment (ASE), this includes all main and where fitted connected sub FDCIE isolate/disable signals. | | | |