Part E4 of the National Construction Code (NCC) sets out the objectives for visibility in an emergency, covering emergency lighting, exit signs (visibility & identification) and warning systems (awareness) in buildings;
E4O1 | Objective | [2019:EO4] |
The Objective of this Part is, in an emergency, to safeguard occupants from injury by— (a) having adequate visibility; and (b) having adequate identification of exits and paths of travel to exits; and (c) being made aware of the emergency. |
In this article, we cover the need for circuit sensing, especially when artificial lights and emergency lights are on separate subcircuits.
When emergency and artificial lighting are on separate final subcircuits in the same area, it’s possible that a failure in the artificial lighting circuit may not trigger the automatic and instantaneous activation of the emergency lights, which may affect the safety of occupants in an emergency.
When the emergency and artificial lights are on separate final subcircuits, the emergency lighting system may not detect the loss of power in the artificial lighting circuit, as there is no direct connection or signal to trigger their activation.
To address this, Australian Standard AS/NZS 2293.1:2018 sets out the requirement for the sensing of the electrical supply of normal lighting circuits as follows;
AS/NZS 2293.1:2018
Clause 1.5.32 Monitored supply
The electrical supply to normal lighting luminaires, failure of which is sensed by the emergency lighting system.
and;
AS/NZS 2293.1:2018
Clause 2.3.3 Sensing of supply failure
Within a designated area the failure of the normal supply to final subcircuits supplying lighting to that area shall cause each emergency luminaire and exit sign in the area served by the subcircuit to be automatically connected to its emergency power source.NOTE: This requirement does not preclude other emergency luminaires and exit signs, connected to subcircuits that might not have lost supply, from also being automatically connected to their emergency power sources in response.
Where any part of a designated area is served by more than one normal lighting subcircuit, the arrangement and connection of the emergency luminaires and exit signs shall be such that the illuminance provided by the normal lighting luminaires on the circuits that are sensed for loss of supply is not inferior to that provided by the required emergency lighting.
In New Zealand, where non-maintained exit signage is used, it shall be configured to be energized in the event of activation of the fire alarm system.
NOTES:
- See Figures C1, C2 and C3 of Appendix C for example circuit arrangements.
- See Clause 3.3 for additional requirements which may impact upon the connection of emergency luminaires and exit signs for testing purposes.
- In New Zealand, where generators are permitted to provide emergency lighting power supplies, refer to Clause F6 of the New Zealand Building code.
Emergency lights on different circuits to normal lighting in the same area
Where an emergency light or lights are on a different final subcircuit from the normal (artificial) lighting in the same area, a "sub-circuit sensing device" or "power sensing device" is required to be installed (typically at or within the electrical switchboard) where the electrical circuits commence.
There are a range of these "sub-circuit sensing device" available from different manufacturers that support the monitoring of one or more separate normal lighting final subcircuits.
These devices solve the problem by sensing the power from one or more normal lighting final sub-circuits and then activating a contactor to enable the operation of the emergency lighting circuit in the same area.
These devices may also include integrated the the required emergency light and exit sign test facilities described in Section 3 of AS/NZS 2293.1:2018.
What to do if these automatic and instantaneous operation features do not exist
Where the automatic and instantaneous operation of emergency lights in a building does not occur when the artificial lighting in that area has failed, then this poses a risk to health, safety and amenity of the building.
Workers conducting tests of emergency lights and exit signs in buildings should verify that the failure of artificial lighting final subcircuits in a given area, operate the emergency lights in that same area.
NOTE: Testing this functionality may pose a problem and risk to the existing occupants of a building for the duration of the test.
To verify the operation of the emergency lights in the same area of the artificial lighting, where the power supply for each is on its own final sub-circuit, the following general procedure may be employed;
Where a failure of the automatic and instantaneous operation of emergency lights in an area is identified, it may be considered a defect for the purposes of satisfying the requirements of the NCC and AS/NZS2293.1
Where the emergency lights fail to operate automatically and instantaneously where power is lost to the artificial (normal) lighting in the same area it may be considered a defect.
This depends somewhat on the date of construction of the building or the date of installation of the emergency lights.
Notwithstanding, people entering a building have a reasonable expectation that the building will be safe to occupy and exit in the event of an emergency. Building owners, agents of owners and occupiers have a responsibility and duty to ensure the safety of the occupants of the building consistent with the Objectives set out in the National Construction Code.
Always the question arises that if the Objective of the NCC and a requirement of the Standard does not exist, is it a defect?
The answer to this question may depend on the date in which the building was constructed and approved or a seperate matter of workplace health and safety.
For most buildings constructed or substantially altered after 2005 will require the facility to monitor the power supply of seperate final sub-circuits in the same area, meaning that an argument can be made that it was a requirement of the the Australian Standard at that time.
From a workplace health and safety standpoint, its reasonable to assume that an occupant of a building should reasonably expect the safe egress from the building in the event of a fire or other emergency where the artificial lighting has failed.
Where a defect of this nature exists, that is the emergency lights do not operate automatically and instantaneously in the event of a power failure of the normal lighting in the same area.
The solution is to scope and install an appropriate power sensing device that operates the emergency lights in the same area.
This will require the supply and installation by an appropriately licensed and experienced electrician of the following;
In this article, we’ve covered the importance of circuit sensing for emergency lighting systems, particularly when normal and emergency lights are on separate final subcircuits.
Without proper circuit sensing, emergency lights may not activate when artificial lighting fails, posing a risk to building occupants. Compliance with the NCC and AS/NZS 2293.1 ensures that emergency lighting activates automatically and instantaneously, providing safety during emergencies.
Maintenance providers, building owners, agents of owners and occupants should ensure that power sensing devices are installed where needed and regularly tested, ensuring the safety of occupants.
Firewize policy is one of continuous improvement, details of products, procedures or methods described within this document are subject to change without notice. All information provided here is believed to be correct at the time of publication.
Every effort has been made to ensure the accuracy of information which is provided in good faith nothing contained herein is intended to incorporate any representation or warranty, either express or implied or to form the basis of any legal relations between the parties hereto, additional to or in lieu of such as may be applicable to a contract of sale or purchase.
This website is provided solely on the basis that users will be responsible for making their own assessment of the matters discussed herein and are advised to verify all relevant representations, statements and information. Firewize does not accept any liability for any injury, loss or damage incurred by use of or reliance on the information.