Smoke Spill Fan ("SPF")

Under AS/NZS 1668.1 a Smoke Spill Fan (SSF) is a dedicated smoke and heat exhaust fan in a building’s smoke control system that runs during a fire to pull hot smoke out of the fire zone and discharge it outside. The purpose of a smoke spill fan is to ensure emergency egress paths tenable and limits smoke spreading to other zones. A smoke spill fan is usually started automatically by a General Fire Alarm (GFA) signal from a fire detection system and can be overridden manually from the Fire Fan Control Panel (FFCP).

Because a Smoke Spill Fan has to keep working while it moves hot gases, the fan, its motor and its power supply must be rated and protected for elevated temperatures for a set period (commonly 200°C for 2 hours, though the required rating depends on the system design and edition of the standard), and its wiring must be fire-rated so the fan keeps running for as long as the smoke control strategy needs it.

    Disclaimer

    In preparing this definition, we have drawn from various sources including Legislation, Codes, Standards and industry information, research and knowledge.  Like the english language, these definitions may subtly change from time to time. As such these definitions are provided solely on the basis that users will be responsible for making their own assessment of the definition and and are advised to verify all relevant representations, statements and information.