Sensitivity Class (ASD)

Sensitivity Class (ASD)

Sensitivity Class is defined in Australian Standard AS 1670.1 to provide a classification system that categorises an aspirating smoke detector (ASD) system based on its smoke obscuration thresholds and maximum allowable transport times, ensuring the system’s performance matches the specific risk profile and environmental conditions of the protected area.

Sensitivity ClassPerformance LevelPrimary PurposeTransport Time (Seconds)
Class AVery High SensitivityEarliest possible intervention in high-airflow environments or critical asset zones (e.g., Data Centres).60 s
Class BEnhanced SensitivityReliable detection where smoke is prone to severe dilution or thermal stratification (e.g., Atriums, Warehouses).90 s
Class CNormal SensitivityStandard fire protection where point detectors are physically impractical to install or maintain (e.g., Voids, Prison Cells).120 s

    Disclaimer

    In preparing this definition, we have drawn from various sources including Legislation, Codes, Standards and industry information, research and knowledge.  Like the english language, these definitions may subtly change from time to time. As such these definitions are provided solely on the basis that users will be responsible for making their own assessment of the definition and and are advised to verify all relevant representations, statements and information.