In the middle of 2025, I came across a Class 2 residential building fitted with what on the surface appeared to be a combined smoke alarm and smoke detection system.
That is wired and interconnected smoke alarms (AS 3786) in each Sole Occupancy Unit (SOU) and a smoke detection system (AS 1670.1) in the common areas and in the Class 7a car park.
On the surface, everything looked ok, but the occupants had concerns and questions.
There was a little history here, so let me indulge by providing a little background on the matter and how the occupants of the building started to have concerns (particularly around the operation of the smoke alarm system).
This particular building was identified as part of a State Government audit of buildings with combustible cladding. The audit identified the building indeed had small amounts of combustible cladding and they would need to take steps to mitigate the increased risk from fire.
One of the mitigations that was recommended by the Municipal Building Surveyor (MBS) was to install additional smoke alarms adjacent to each outward facing opening (windows and doors) for each SOU.
This would give the occupants of the building an increased likelihood of early detection and alarm in the event of an external fire, and because the smoke alarms are wired and interconnected, that means all smoke alarms should activate in each SOU if any one smoke alarm activated.
According to the Municipal Building Surveyor, this seemed to be a reasonable concession given the relatively small amount of combustible cladding identified.
As a Class 2 residential building, there was also a Owners Corporation (OC). An owners corporation is responsible for managing common property in properties with subdivided lots, like apartment buildings, managing finances, maintaining shared areas (gardens, lifts, etc.), taking out insurance, and ensuring compliance with the relevant laws and the property's rules.
The Owners Corporation had engaged an Owners Corporation Manager to act on behalf of the lot owners. Their role was to oversee the administration, finances, maintenance, and compliance of the common property.
To comply with the direction given by the Municipal Building Surveyor, the OC Manager sought advice from the building’s incumbent fire services contractor about the best way to comply with the direction provided by the Municipal Building Surveyor.
The incumbent specialist service provider conducted a site inspection and found the existing fire alarm panel, smoke detectors, heat detectors and smoke alarms were obsolete and needed to be replaced as part of the larger compliance project.
This is where things started to go in the wrong direction.
For the sake of those involved, I am not going to provide any commentary on what happened next, but rather focus on another question that the specialist fire services contractor could have considered.
What was the best path to replace the existing obsolete smoke alarm system and fire detection and alarm system, given the existing infrastructure and compliance obligations?
We now need to start to dig deeper into the options available for compliance, set out in the National Construction Code, and in particular, Specification 20 that covers “smoke detection and alarm systems”.
Specification 20 of the National Construction Code (NCC) describes the installation and operation of automatic smoke detection and alarm systems in Class 2 to Class 9 buildings.
According to convention and the National Construction Code there are TWO types of required automatic smoke detection and alarm systems plus a third option that is a combination of these two systems.
In this article, we will explore how these systems can be used in each building classification. To understand the requirements, apply, we must understand the “type of system” described in Specification 20;
Reading the text here is a little complex, so let's try and summarise it in table form;
In simple terms, wherever a smoke alarm system (S20C4) could be installed, a smoke detection system (S20C4) or a combined smoke alarm and smoke detection system (S20C5) may be used1, BUT a smoke alarm system or a combined smoke alarm and smoke detection system may never be used where a smoke detection system is required.
Another simpler way to put it is this: a smoke alarm system can be used in the following circumstances;
Other than the titles of these systems, “smoke alarm system” or “smoke detection system”, what are the key differences, and why would I choose one over the other?
A smoke alarm system, as defined under Clause S20C3 of the National Construction Code (NCC), refers to mains-powered, wired and interconnected self-contained smoke alarms that are typically installed within each sole-occupancy unit (SOU) of a residential building.
Australian Standard AS 3786 is the Standard that covers Smoke Alarms that include an integrated smoke sensor, an audible alarm, and test facility. They are designed primarily for occupant warning and in the case of a Class 2 building, must be hard-wired and interconnected so that activation of one alarm triggers all other smoke alarms within the same SOU.
In contrast, a smoke detection system, compliant that satisfies Clause S20C4 and complies with Australian Standard AS 1670.1, includes a Fire detection Control & Indicating Equipment (FDCIE), and is typically used in more complex or environments. These systems include various interconnected components like smoke detectors, heat detectors, a control panel, and occupant warning system.
A combination smoke alarm and smoke detection system employs elements of both systems, typically with smoke wired and interconnected smoke alarms in each SOU, with a smoke detection and alarm system used in the common areas of the building with an integrated occupant warning system.
A Class 9a building where 6 or less bed patients are accommodated may use a smoke alarm system or a smoke detection system, but not a combined system.
YES, a Smoke Detection System may be used for a Class 2 building in lieu of a Smoke Alarm System or combined system, but there are additional requirements described in both Australian Standard AS 1670.1 and the Specification 20 as generally follows;
This article looks at smoke alarm and detection systems in Class 2 buildings, focusing on a real example that placed the occupants of the building at risk. The building in question had a combination setup—interconnected smoke alarms (AS 3786) in each SOU and a smoke detection system (AS 1670.1) in the common areas and car park. Everything looked compliant on the surface, but concerns were raised following a cladding audit.
The Municipal Building Surveyor recommended extra smoke alarms near windows and doors to help detect fires that may start outside. This led to questions about the best way to upgrade the existing (and outdated) systems while staying compliant with the NCC.
Specification 20 of the NCC outlines three valid options for Class 2 buildings: a smoke alarm system, a smoke detection system, or a combination of both. This article unpacks the key differences between them, when each can be used, and highlights that while a detection system can be used in Class 2 buildings, it brings additional obligations around detector placement and sound levels.